The SID system monitor is designed as the central controller for the IKON AVS fault detecting system intended to monitor life safety critical public address systems.

SID


Due to the systems flexibility and fault tolerance it may be used to monitor and report the operational status of:-

 
Individual speaker stacks during live audio.
 
Signal level audio distribution systems.
 
Any system that provides digital status or voltage outputs.

SID monitors up to 250 outlying fault detection devices, these can be any combination of the following IKON AVS units:-

 
ECM.
Eight-channel speaker line monitor.
 
DRS.
Digital interface, which monitors the state of 24 digital inputs.

All communications between the fault detectors and SID use a proprietary fault tolerant dual fibre network. Both fibre loops are continuously monitored to ensure their integrity and if a fibre fault is detected, SID will log the faults identifying where in the network the failure has occurred. Due to the networks inherent fault tolerance, partial systems can be operated during installation.

A comprehensive array of LED’s and displays are used to confirm the systems operation as well as providing a local indication of fault occurrence, printer fault or network problems. The 4 line, 20 character LCD display is used to display the event no. complete with a time and date stamp as well as  a short textual description of the fault and originating unit.

A system can support two SID’s in a Master / Slave configuration.

System Interconnections

Transmit
Twin ( Primary & Secondary ) ST fibre connectors for the outgoing fibre connections to other elements of the system. The system is software configurable for single or dual fibre operation.
Receive
Twin ( Primary & Secondary ) ST fibre connectors for the incoming fibre connections from other elements of the system. The system is software configurable for single or dual fibre operation with correct operation verified and reported.
Serial
Provides serial event messages to third party logging equipment
Event Relay
A change over relay that can be configured to provide a change in status on the detection of a fault only or on any change in fault status. This output is suitable for linking to an external sounder.
Printer Out
For connection to a dot matrix or inkjet printer for printing of fault reports with a time and date stamp.
Program
With the socket provided on both the front and rear panel, a laptop computer can be
connected to this port for configured the SID and also for downloading fault logs that include a time and date stamp.
SID utility image

Software

A Windows based software utility is supplied for configuring not only the SID but also all the network devices on the fault monitoring system. Each network unit is given a unique ID and name with these reported to SID. Each fault status on the remote units is also named and stored within SID for display on the LCD screen and printing.

Engineering Specification

Max number of external devices
250
Max number of messages per device

ECM = 3 per LS channel ( 24 ) + 4 event inputs
DRS = 24 event inputs

System Memory
2048 messages
Common fault out
Change over relay, 1A 30V DC
Size
482mm (W) x 88mm  [ 2u ] (H) x 250mm (D), excluding connectors
Weight
4Kg
Power requirements
40mA @ 240V AC,    300mA@ 24V DC