System Interconnections

Group

Six separate inputs for connection to four external sensors per group. Separate connections are provided for 12V and 24V sensors as well as access to the internal 12V PSU.

Common Fault

A change over relay provides a common fault output that can be configured to provide a change in status for any fault occurrence.

Transmit & Receive

Twin ( Primary & Secondary ) ST fibre connectors for the fibre connections to other elements of the system. The system is software configurable for single or dual fibre operation.

Software

A Windows based software utility is available for use with the unit allowing simple system configuration and adjustments. The software allows unit identification, selection of monitoring type, configuration of the Event Input and Common Fault output as well as monitoring of Mains & DC supplies.

Event inputs

Six groups of four. Each can be set for active Hi or active Lo and can also be given a fault description. Leave Active unchecked to inhibit an input from reporting.

Engineering Specification

Group Inputs

12V DC @ 15mA, 24V DC @ 15mA.

Common fault out

Change over relay, 1A 30V DC

Size

482mm (W) x 88mm  [ 2u ] (H) x 250mm (D), excluding connectors

Weight

4.5Kg

Power requirements

60mA @ 240V AC, 200mA@ 24V DC ( excluding external 12V out)